qiao@hvtest.cc15871365102
  • UHV-220/30F Battery Discharge Tester Analyzer

    UHV-220/30F Battery discharge tester system the voltage monitoring information of single battery is simple, safe and accurate with wireless relay access. There is perfect protection function, not only sound, light warning, but also a clear interface tips of the equipment.

    Product Details of UHV-220/30F Battery Discharge Tester Analyzer


    Product Introduction

    After years of research and development, our company has successfully developed a series of high-intelligence, high-precision battery discharge testers using our proprietary technology.

    The discharge tester can operate in offline mode, using the battery as the discharge load. By continuously regulating the discharge current, it maintains a constant discharge current at the set value. During discharging, the instrument will automatically stop when any of the following conditions is met: the battery terminal voltage or individual cell voltage falls to the preset lower limit, the set discharge time is reached, or the set discharge capacity is achieved. Throughout the process, all valuable and continuous real-time data is recorded.

    The battery discharge tester system uses wireless relay access to collect voltage monitoring information from individual cells in a simple, safe, and accurate manner.

    The tester features a highly user-friendly interface, allowing users to complete various settings and data queries under menu prompts. Discharge process data can be saved in the device's internal memory and transferred to a USB drive via the data interface. The data can then be analyzed using dedicated PC software to generate required curves and reports.

    The battery discharge tester is equipped with comprehensive protection functions, including audible and visual warnings, as well as clear on-screen interface prompts to ensure safe operation.


    Technical Parameters

    Working modecan be used alone, can be used simultaneously, can be remote control and status monitoring
    Applicable battery48V110V220V380V

    other electrical test

    groups can be customized

    Discharge voltage0~60V88~132V176V~275V300V~456V
    Discharge current0~150A0~100A0~100A0~30A
    Accuracy of current1%
    Voltage accuracy0.5%
    Monomer voltage accuracy0.2%
    Monomer voltage0.500V~16.00V(resolution 1mv)
    Charge discharge time0 ~ 99 hours and 59 minutes
    Power supplyAC:220V
    Cooling wayforced air cooling
    Packagingaluminum alloy pull box

    Work Environment

    Heat dissipationforced air cooling
    Temperatureworking range: -5 ~ 50℃ storage temperature: -40 ~ 70℃
    Humidityrelative to humidity0 ~ 90% (40±2℃)
    Altituderated altitude: 4000 m
    Noise﹤60dB


    Working Power Supply

    Voltagesingle-phase three-wire system: 220V AC (- 20% ~ +30%), frequency :45 ~ 65Hz
    Withstand voltage testinput - housing: 2200V DC 1min
    input-output: 2200V DC 1min
    output - housing: 700V DC 1min
    Securitymeet EN610950


    Wiring

    AC inputGb socket, suitable for 1 ~ 1.5mm2cable
    DC outputinstrument 25 mm2Cable quick connect plug (red positive black negative)


    Product Characteristics

    Constant Current Discharge Function: Continuously adjustable current enables accurate battery capacity measurement.

    Wireless Cell Voltage Monitoring: Each wireless monitoring module can simultaneously monitor up to 12 individual cells.

    PC Analysis Software with Remote Control: Includes Chinese-language background analysis software and supports remote-controlled discharge functionality.

    Data Interface & Storage: The host is equipped with a USB interface and 2GB of high-capacity internal data storage.

    Dual CPU Operation: Dual processors work together to ensure test safety, reliability, and accuracy.

    Flexible Discharge Control: Discharge can be paused and parameters modified without terminating the discharge test.


    Maintenance and after-sales service
    Possible field failures
    Voltage alarm: after connecting the large current wire, the machine keeps alarms to check whether the positive and negative poles and the voltage range are within the rated voltage range of the nameplate.
    During the discharge process, the "discharge current fault air switch is abnormal" is displayed.
    Check whether the discharge switch has been closed.
    The discharge current is normal during the discharge process, but the voltage does not drop. The battery pack may not leave the UPS charging system.
    Discharge: the total voltage is not collected, the total voltage acquisition line is not connected, or the reverse, or the line in the middle of the collection line.
    Optional: the single voltage on the site is not consistent with the site, please check whether the wiring harness of the wireless acquisition box is wrongly connected. Generally, the wrong cross connection will show abnormal voltage values such as 5V, 17V. The field wireless single collection voltage collection is not normal, please check the multimeter, or check whether the wiring is wrong. And the actual battery number (some factory battery pack standard number, not according to the actual series sequence number.)


    after-sale service

    The company has a one-year warranty for the products sold(if the contract is not guaranteed separately, the contract shall prevail). Please contact the after-sales service department for your customer maintenance.
    Maintenance cost receivable for any of the following conditions during the warranty period:
    1. Failure or damage caused by impact during user use or handling.
    2. The user is not properly keep, resulting in water seepage, moisture, impact or fire, etc.
    3. Fault or damage caused by maintenance by users or by other units.
    4. Equipment is faulty or damaged due to wiring error.
    5. such as force majeure (such as fire, flood, natural disaster, etc.).
    6. Fault or damage caused by not connecting other equipment according to the requirements of the instructions.
    7. No product warranty card and can not confirmthat the instrument is in the warranty period of the fault products.








    You Might Also Like

    • Have Any Questions!

      DON'T HESITATE TO CONTACT US ANY TIME
      Contact us
    • Visit Us

      Building 6, Optics Valley Optical-Mechanical Industrial Park, 84 Gaoxin 5 Road,
      East Lake New Technology Development Zone, Wuhan City, Hubei Province, China

    • Email Us

      qiao@hvtest.cc

    • Call Us

      +86-15871365102